SAFE-T Connect

                                                                                        Application field

Safe-T_Connect

The SYR Safe-T Connect 2421 has a leakage protection according to VP 638, which permanently monitors the installation as soon as it is activated. It fits onto any flange of the SYR flange system up to DN 32. The module can be fitted with any fitting, which can also be mounted on the flange. The Safe-T can also be used as a stand-alone version and can be controlled via the Internet.

Performance

The monitoring electronics of the Safe-T Connect allow detection of leakages. If the pre-programmed values are exceeded, the entire installation is locked. The Safe-T provides a holiday function for enhanced monitoring. The management and diagnostics system allows individual setting of all important function data.

Materials

The housing is made of high-quality, lead-acid brass alloy. The rubber parts are made of aging-resistant elastomers. Stainless steel is used for all other functional parts. All materials used comply with the recognized rules of technology. All plastic parts touched by the water comply with the KTW recommendations of the Federal Health Office.

Installation

To mount the Safe-T Connect a flange DN 20 – DN 32 from the extensive Drufi flange program is required. It can be installed either centrally behind the water metering system in the pipeline or decentrally to single strand protection. The Safe-T Connect is used as a combiner for e.g. With a Drufi or also individually.
Safe-T Masszeichnung

Mounting

Before installation, thoroughly rinse the pipeline. The need for connection SYR-flange can be installed free of stress, taking into account the direction of flow in vertical and horizontal lines. All electrical connections are factory pre-assembled.

Maintenance

The Safe-T Connect allows a maintenance-free operation of the device.

Technical Facts

Operating temperature:  max. 30 °C
ambient temperature:  10 – 60 °C
Rated pressure:  16 bar
built-in: Main axis vertical
 Medium: Drinking water
Protection class:  IP 21
batteries:  4 x LR06
Power supply:  9V DC
External load  IN 2: at least 12V / 20 mA
potential-free contact:  Out: max. 24V / 2A
Starting threshold:  5 Liter/h
Flow rate:  DN 20: 2.0 m3/h bei 0,2 bar Δp
 DN 25: 2,3 m³/h bei 0,2 bar Δp
 DN 32: 2,5 m³/h bei 0,2 bar Δp
 DN 20: 3,5 m3/h bei 0,5 bar Δp
 DN 25: 3,8 m³/h bei 0,5 bar Δp
 DN 32: 4,0 m³/h bei 0,5 bar Δp
 DN 20: 5,2 m3/h bei 1,0 bar Δp
 DN 25: 5,7 m³/h bei 1,0 bar Δp
 DN 32: 6,0 m³/h bei 1,0 bar Δp